Description of heat flux measurement methods used in hydrocarbon and propellant fuel fires at Sandia. [electronic resource]

 0 Người đánh giá. Xếp hạng trung bình 0

Tác giả:

Ngôn ngữ: eng

Ký hiệu phân loại: 621.4038 Prime movers and heat engineering

Thông tin xuất bản: Albuquerque, N.M. : Oak Ridge, Tenn. : Sandia National Laboratories. ; Distributed by the Office of Scientific and Technical Information, U.S. Dept. of Energy, 2010

Mô tả vật lý: Size: 62 p. : , digital, PDF file.

Bộ sưu tập: Metadata

ID: 267589

The purpose of this report is to describe the methods commonly used to measure heat flux in fire applications at Sandia National Laboratories in both hydrocarbon (JP-8 jet fuel, diesel fuel, etc.) and propellant fires. Because these environments are very severe, many commercially available heat flux gauges do not survive the test, so alternative methods had to be developed. Specially built sensors include 'calorimeters' that use a temperature measurement to infer heat flux by use of a model (heat balance on the sensing surface) or by using an inverse heat conduction method. These specialty-built sensors are made rugged so they will survive the environment, so are not optimally designed for ease of use or accuracy. Other methods include radiometers, co-axial thermocouples, directional flame thermometers (DFTs), Sandia 'heat flux gauges', transpiration radiometers, and transverse Seebeck coefficient heat flux gauges. Typical applications are described and pros and cons of each method are listed.