Doubly-fed induction generator wind turbines are very sensitive to grid disturbances, especially to voltage dips, since they are connected directly to the grid. The ability of a wind turbine to survive a short voltage dip without tripping is referred to as the low-voltage ridethrough (LVRT) capability. Crowbar, dynamic voltage restorer (DVR) and energy storage system (ESS) are the solutions which are adopted in this study. In order to test the LVRT capability of the wind turbine system, the PSCAD/EMTDC simulation has been performed for a 2 MW DFIG wind turbine system. In comparison of the LVRT techniques, although the ESS, with relatively high cost, outperforms the crowbar, the DVR system presents the best performances of the wind turbines through keeping the stator voltage at constant under grid fault condition despite the balanced and unbalanced voltage dips as well as normal condition.Keywords: Crowbar, doubly-fed induction generator (DFIG), dynamic voltage restorer, energy storage system, voltage sag.Máy phát điện gió loại không đồng bộ ba pha nguồn kép rất nhạy cảm với các nhiễu của lưới, đặc biệt là giảm áp lưới. Khả năng một tua-bin gió tiếp tục duy trì kết nối lưới khi có giảm áp lưới trong thời gian ngắn mà không bị ngắt được gọi là khả năng lướt qua điện áp thấp (LVRT). Các giải pháp như crowbar, bộ phục hồi điện áp động (DVR) và hệ thống lưu trữ năng lượng (ESS) được nghiên cứu để đảm bảo vẫn duy trì kết nối lưới khi có giảm áp. Bài báo trình bày các kết quả nghiên cứu và đánh giá các giải pháp điều khiển để thấy được khả năng vượt trội của chúng. Hệ thống DVR thể hiện đáp ứng vận hành tốt nhất thông qua việc giữ điện áp stator của máy phát không đồng bộ ba pha nguồn kép (DFIG) bằng hằng số khi có giảm áp cũng như điều kiện bình thường.Từ khóa: Bộ phục hồi điện áp động, crowbar, độ giảm điện áp, hệ thống lưu trữ năng lượng, máy phát điện không đồng bộ ba pha nguồn kép